Rated power | VA/W | 1000VA/800W | 2000VA/1600W | 3000VA/2400W |
AC input | Input system | Single phrase & earth ground |
Ranged voltage | 220VAC |
Frequency | 50Hz |
Voltage range | 115~300VAC |
Frequency range | 45~55Hz |
Voltage range of bypass | 80VAC~285VAC |
DC input | DC nominal voltage | 24VDC/48VDC/110VDC/220VDC |
24V | Nominal current | 40.0A | 78.4A | 117.6A |
Voltage range | 20-29VDC |
Input low voltage/protection | 20/21VDC |
Input high voltage/protection | 29/29VDC |
48V | Nominal current | 19.6A | 39.2A | 58.8A |
Voltage range | 40-58VDC |
Input low voltage/ protection | 40/42V |
Input high voltage alarm/protection | 58/58V |
110V | Nominal current | 8.6A | 17.2A | 25.8A |
Voltage range | 90-130V |
Input low voltage/protection | 90/95V |
Input high voltage/protection | 130/130V |
220V | Nominal current | 4.3A | 8.6A | 12.9A |
Voltage range | 180-260V |
Input low voltage/protection | 180/190V |
Input high voltage/protection | 260/260V |
AC Output | Output system | Single phase & earth ground |
Output voltage | 220VAC±3%(inverter output) |
Output frequency | 50±5Hz(normal), 50Hz±1%(abnormal) |
Dynamic voltage transient range | <5% |
Dynamic transient restore | < 60ms |
Waveform | Sine wave THD<3%(linear load), sine wave THD<8% (nonlinear load) |
Output power factor | 0.8 |
Overload capability | 105~125%≥ 60s, 126~150%≥30s, the recover point is 90% |
Input current peak coefficient | 3:1 |
Transfer time | 0ms |
Panel indicator system | LED screen + LCD indicator, show the status of inverter and operation parameter |
Communications | RS232(turn to 485), stem node |
Alarm function | AC/DC input under abnormal, overload condition and inverter problems |
Protection function | AC input or output above or below the range of voltage Overload, over temperature and short circuit protection |
Conduction | Satisfy YD/T983-1998A |
Radiation | Satisfy YD/T983-1998A |
Noise immunity | Satisfy YD/T983-1998A |
Insulating resistance | > 2MΩ(500VDC) |
Insulating strength | 2121VDC(AC input, output to ground, DC input to AC output, without flashover in one minute) |
Cooling system | Wind cooling |
Frequency | <55dB(1M) |
Working environment | Temperature | -10'C~+40'C |
Humidity | 0~95%, no condensation |
Altitude | ≤1500M, satisfy GB3859.2-93 |
Storage environment | Inverter temperature | -40'C~+65'C |
Humidity | 0~95%, no condensation |
Dimensions(W×D×H)(mm) | 438×380×83 |